(I) ~n every overhead line all conductor.s shall be :::.headefficiently msulated and secured, and every precautiOn shall be
taken to prevent such conductors from falling away from their
supports.
(2) Adequate means shall be provided to render any such live
conductor dead in the event of its falling, due to breakage or
otherwise.
(3) In the design of such overhead lines the minimum factors
of safety shall apply to each support and shall refer to the
breaking load of the structure. Such minimum factors of
safety shall be subject to the approval, in writing, of the Chief
Inspector of Machinery.
(4) Such overhead lines may be erected along or across
thoroughfares, roads, railways, tramways or buildings subject
to the prior approval, in writing, of an Inspector who may
impose thereon such conditions as he may consider necessary.
(5) No overhead line conductor shall cross over or under any
other line conductor without efficient precautions being taken
to prevent the contact of such conductors.
(6) The minimum vertical height of electrical conductors and
other wires from the ground, except in the case of electric trolley
wires and service lines for lighting domestic use and telephone
lines, shall be sixteen feet.
(7) No overhead lines shall be erected nearer than 300 feet
to any explosive magazine, except with the previous approval,
in writing, of the· Chief Inspector of Machinery.
(8) All supports shall be of substantial construction and shall
be placed at intervals of not more than 200 feet apart when the
direction of the line is straight, and of not more than 150 feet
apart when the line is not straight, provided that such intervals
may be varied with the approval, in writing, of the Chief
Inspector of Machinery.
1858 Cap. 218] Machinery (Safe Working &; Inspection)
Underground
cables.
Insulation
or earthing
of certain
parts of
electrical
apparatus.
(9) Service lines shall be connected to line conductors at a
point of support only and shall be efficiently insulated.
{10} All systems of overhead lines shall be suitably protected
against the effects of atmospheric electricity.
(11} No telephone lines shall be placed on the same support
as other overhead lines except for the purpose of direct communication between power houses and sub-stations and then
only with the prior approval of the Chief Inspector of Machinery.
(12) Every overhead line, including its supports and all
structural parts and all electrical appliances and devices belonging to or connected with the line, shall be regularly inspected
and efficiently supervised and maintained as regards electrical
and mechanical conditions.